| Customization: | Available |
|---|---|
| Max Diameter of Workpiece: | <500mm |
| Mass Scope of Workpiece: | 900kg |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
| Accuracy | Cx | ±(reading×1%+1pF) |
| tgδ | ±(reading×1%+0.00040) | |
| Anti-interference index | Frequency conversion anti-interference, in 200% interference can still achieve the above accuracy | |
| Capacitance range | internal high voltage | 3pF~60000pF/10kV 60pF~1μF/0.5kV |
| external high voltage | 3pF~1.5μF/10kV 60pF~30μF/0.5kV | |
| resolution | maximum to 0.001pF, 4 significant digits | |
| tgδ range | No limitation, resolution 0.001%, capacitance, inductance, resistance can be automatically identified | |
| Test current range | 10μA~5A | |
| Internal high voltage | voltage setting range | 0.5~10kV |
| maximum output voltage | 200mA | |
| voltage lifting mode | voltage setting arbitrarialy | |
| test frequency | single frequency set at will( 40-70hz). Automatic dual variable frequency set at will (from 50±0.1Hz to 50±10Hz) Automatic dual variable frequency set at will (from 60±0.1Hz to 60±10Hz) |
|
| frequency resolution | ±0.01Hz | |
| External high voltage | Maximum test current 5A, power frequency or variable frequency 40-70hz, during positive connection | |
| Maximum test current 10kV/5A, power frequency or variable frequency 40-70hz, during reverse connection | ||
| CVT self-exciting low voltage output |
Output voltage 3-50V, output current 3-30A | |
| Measuring duration | About 40s, depending on measuring method | |
| Input power | 180V ~ 270VAC, 50Hz ± 1% | |
| Computer interface | Standard RS232 interface | |
| Pinter | mini-type thermal printer | |
| Ambient temperature | -10ºC~50ºC | |
| Relative humidity | <90% | |
| Dimensions | 460×360×350mm | |
| Weight | 28kg | |